see this hard drive? earlier we sent a datacenter technician to swap a few broke...
alina🐾💖✨🏳️⚧️ @alina@girldick.gay
see this hard drive? earlier we sent a datacenter technician to swap a few broken drives and as he was standing next to this server, the drives got 7-10 degrees celsius hotter because his body was blocking the fans' exhausts
so this made us investigate our servers' airflow in correlation to S.M.A.R.T. temperature value, and turns out that for huge chunks of our custom spine-leaf architecture and rackserver format, the static air pressure from the hot aisle coming from 15k RPM fans for enterprise customers is too strong as that the cheap budget fans for our Ceph product could compete against it, and is getting pushed back into the cold aisle -.-