Things you don't notice until you actually get the instrumentation to study it: ...
Andrew Zonenberg @azonenberg@ioc.exchange
Things you don't notice until you actually get the instrumentation to study it: some of my smaller IT gear has a terrible power factor.
The average power factor of my main IT rack lower PDU (running most of the servers and switches) is an excellent 0.99 with about 1 kW of load.
The upper PDU on the main rack is averaging 0.86 with about 350W load, with the main offenders being the FS 1G edge switch (14W @ 0.58 PF) and the PoE injector (48W @ 0.57 PF).
But the PDU on the development/UPS rack is a different story. It's averaging 0.76 with 133W / 175 VA load.
The Xilinx AC701 is last place with 9W of active power and a whopping 0.42 PF. The USB PD dongle for [redacted board] is only slightly better with 6W at an 0.49 PF, then the powered USB hub is pulling 7W at 0.59 PF, and the Siglent SPD3303X-E is pulling 25W at an 0.65 PF.
The NUC is pulling 7W at an 0.75 PF and the only reason my average isn't a lot worse is the old 24-port Cisco switch pulling almost 80W at an 0.96 PF - probably the only thing on the rack that actually has deliberate PFC.