Power outage in data! Let's start with the overall house. There's a bunch of int...
Andrew Zonenberg @azonenberg@ioc.exchange
Power outage in data! Let's start with the overall house.
There's a bunch of interesting things we can see:
1) The maintenance window on Tuesday working in the main electrical panel. Most of the lab was powered down during this time, so no data was being collected.
2) A smaller dropout due to followup reboots and cluster reconfiguration later in the same maintenance window.
3) From about 18:00 to 20:00 today, grid power is lost. The lack of data from the solar gateway seems to be triggering a bug in my monitoring scripts I'll have to look into (that gap should be rendering as green, not blue).
During the utility outage the lab UPS and a few other critical loads were running on generator, but I do not have metering at the transfer switch so the only consumption numbers I actually have are for the lab UPS (which was essentially unchanged at ~2 kW after my recent load shedding optimizations).
I expect there were another few hundred watts from the fridge, TV, lab HVAC, et (kid was watching some cartoon during the outage), but that data is lost. When I refill the propane tank I can get a total fuel consumption number, though.
Finally, after grid power returns, we see a surge to over 8 kW. This is likely things like the house HVAC and the water heater all firing up at once to get back to their happy place. I took a shower during the outage which was fine since the water tank was warm, but that left the tank well below normal operating temperature.