A false smoke alarm almost drowned Jane Street's only NYC datacenter michael.bac...

@best30

A false smoke alarm almost drowned Jane Street's only NYC datacenter michael.bacarella.com · 260 points · 132 comments · HN thread

TL;DR A systems engineer at Jane Street recounts how a dust-triggered smoke alarm in the firm's only NYC datacenter (at 1 New York Plaza) shut down the cooling via the alarm wiring, pressurizing the sprinklers and threatening to heat the room past 150 F. He ran across the building to pull power cords on every server before temperatures topped out near 143.6 F, then wrote an OCaml monitor that averages server temperatures every minute and alerts on a fleet-wide rise. The thread mostly drifts into Hurricane Sandy diesel-hauling stories and a debate over whether heroic firefighting reflects bad planning, with some commenters questioning the lack of an emergency power-off button and sprinkler choice.

  • Contractors cutting into materials in a prep room next to the datacenter kicked up dust that set off the smoke alarm.
  • The smoke alarm was wired to shut down the CRAC cooling units, while the sprinkler heads were pressurized and would open once heat rose, creating a risk of overheating the room.
  • The author ran from his nearby apartment, pulled power cords on every server row by row, and watched the room temperature peak at about 143.6 F before it stopped climbing.
  • Hong Kong staff had noticed the overheating only by chance on a display showing many servers warming at once, which motivated the author's monitoring tool.
  • The new monitor, written in OCaml, polls each Linux server's onboard temperature sensors every minute and alerts the systems team when the average rises.
  • Jane Street kept its sprinklers and tightened procedures and surveillance rather than moving the machine room, until Hurricane Sandy later changed the picture.

Discussion The thread is long and wide-ranging, and it moves away from the smoke alarm quickly. Many commenters share their own Hurricane Sandy experiences, including hauling diesel up stairs, failed fuel inlets and clogged filters, and a quant-firm-adjacent telephony company that moved traffic out of NYC. A second strand debates whether heroic last-minute efforts are admirable or evidence of poor planning, and a third questions the datacenter design itself: missing emergency power-off buttons, sprinklers versus gas suppression, and whether the story is AI-written. The mood is mostly appreciative and anecdotal, with a sharper edge in the planning debate.

  • Sandy-era stories and anecdotes are the most engaging part (many): Many commenters share first-hand disaster stories from Hurricane Sandy, including diesel hauling, flooded fuel inlets, and generator filter problems. These stories often value the practical lessons more than the Jane Street incident itself.
  • Heroic recovery often hides poor planning (some): Several commenters argue that celebrating people who haul fuel or work marathon hours praises failures of planning and leadership. They point to Fog Creek's lack of backups as an example of a failure being lionized.
  • Heroism and systemic failure can both be recognized (some): Others respond that people who go beyond the call of duty deserve recognition regardless of what caused the emergency, and that good organizations should then investigate the root cause.
  • A physical emergency power-off button should have existed (some): Several commenters are surprised there was no EPO button or EPO-linked shutdown, which code often requires. Others note that unplugging hardware is safer than an untrained person operating electrical panels.
  • Sprinklers are a poor choice for datacenters (a few): A few commenters find water-based sprinklers absurd for servers and point to clean agents, while others note that gas suppression is hazardous in occupied office buildings and can damage hard drives via acoustic effects.
  • Engineers should negotiate pay for on-call duty (a few): One thread argues that employees who mention personal details or their proximity to the office end up doing unpaid emergency work, and advises setting boundaries and asking for raises.

Links from the comments

#datacenter #fireSuppression #incidentResponse #JaneStreet #HurricaneSandy #OCaml